Only if you download our software and practice no more than 30 hours will you attend your test confidently. Because our CDCS exam torrent can simulate limited-timed examination and online error correcting, it just takes less time and energy for you to prepare the CDCS exam than other study materials. It is very economical that you just spend 20 or 30 hours then you have the CDCS certificate in your hand, which is typically beneficial for your career in the future. Therefore, purchasing the CDCS guide torrent is the best and wisest choice for you to prepare your test.

EXIN certification CDCS exam is one of the many IT employees' most wanting to participate in the certification exams. Passing the exam needs rich knowledge and experience. While accumulating these abundant knowledge and experience needs a lot of time. Maybe you can choose some training courses or training tool and spending a certain amount of money to select a high quality training institution's training program is worthful. PrepAwayTest is a website which can meet the needs of many IT employees who participate in EXIN Certification CDCS Exam. PrepAwayTest's product is a targeted training program providing for EXIN certification CDCS exams, which can make you master a lot of IT professional knowledge in a short time and then let you have a good preparation for EXIN certification CDCS exam.

>> Dumps CDCS Discount <<

2025 Dumps CDCS Discount - The Best EXIN EXIN EPI Certified Data Centre Specialist - Guaranteed CDCS Questions Answers

As we know, information disclosure is illegal and annoying. Of course, we will strictly protect your information. That’s our society rule that everybody should obey. So if you are looking for a trusting partner with right CDCS guide torrent you just need, please choose us. I believe you will feel wonderful when you contact us. We have different CDCS prep guide buyers from all over the world, so we pay more attention to the customer privacy. Because we are in the same boat in the market, our benefit is linked together. If your privacy let out from us, we believe you won’t believe us at all. That’s uneconomical for us. In the website security, we are doing well not only in the purchase environment but also the CDCS Exam Torrent customers’ privacy protection. We are seeking the long development for CDCS prep guide.

EXIN CDCS Exam Syllabus Topics:

TopicDetails
Topic 1
  • Data Centre Life Cycle and Standards: This section of the exam measures the skills of data center professionals and covers the various stages involved in the life cycle of a data center, from planning and design to implementation and decommissioning.
Topic 2
  • Designing and Implementing a Data Centre: In this module, the exam assesses the knowledge of Exin data center professionals tasked with the design and implementation of data centers. Candidates will learn the key principles of creating an efficient data center layout, including considerations for scalability, redundancy, and security.
Topic 3
  • Data Centre Environmental Considerations and Efficiency: This section evaluates the proficiency of data center professionals in addressing environmental factors and promoting efficiency within data center operations. The target audience, including data center managers and engineers, will be tested on their ability to identify and implement measures that enhance energy efficiency, cooling management, and sustainable practices.

EXIN EPI Certified Data Centre Specialist Sample Questions (Q49-Q54):

NEW QUESTION # 49
The pipes of a VESDA smoke detection system are installed at the air intake of the air conditioner inside the computer room.
Is this a good practice from an early smoke detection point of view?

  • A. No, the piping should be installed at the air exhaust of the air conditioner, as there can also be a fire inside the air conditioner itself.
  • B. It depends on the type of gas-based fire suppression which will be installed.
  • C. Yes, as this reduces the amount of piping to be installed in the data center, as all air will go through the air conditioner.
  • D. No, it will give a longer reaction time for the smoke detection system and there might also be bypass airflow.

Answer: D

Explanation:
For optimal early smoke detection in a data center, it is crucial that the Very Early Smoke Detection Apparatus (VESDA) system be installed at locations where smoke will be detected as soon as it appears. Positioning the VESDA pipes at the air intake of the air conditioner inside the computer room is not ideal. This placement could result in a delayed detection response and the potential for bypass airflow to occur, which would impede the system's ability to detect smoke effectively.
Detailed Explanation:
When VESDA pipes are installed at the air intake, the detection system relies on the smoke to be drawn into the air conditioning unit before detection can occur. This setup increases the reaction time as the smoke has to travel through the intake and get processed by the air conditioner. Furthermore, bypass airflow-a phenomenon where not all the air containing smoke particles passes through the VESDA pipes-could also delay or even prevent the system from detecting smoke early.
Ideally, VESDA pipes should be positioned where smoke is likely to accumulate first, such as near the ceiling or in the return airflow path to detect smoke at the earliest possible stage. This ensures that the detection system can quickly trigger alarms, providing more time to address potential fire hazards.
EPI Data Center Specialist References:
EPI Data Center Specialist training highlights that smoke detection should prioritize early response capabilities to maximize safety. The preferred installation for VESDA pipes is generally at points where smoke would naturally accumulate, rather than relying on air conditioning intakes where airflow can vary and delay detection. In their course materials, EPI emphasizes minimizing reaction time and reducing the impact of airflow dynamics on smoke detection efficiency.


NEW QUESTION # 50
You are working with a customer who requires a guarantee that THDi levels coming from the UPS should not exceed more than 3% THDi. Furthermore, he wants to run a power-efficient data center. The UPS has a 6-Pulse SCR/Thyristor based rectifier. The current load on the UPS is approximately 80%. The customer indicates they are not expecting any changes on the ICT infrastructure for the next 3 years.
What should you recommend?

  • A. Nothing, the UPS will be able to take care of the right levels of THDi
  • B. Install an active harmonic filter on the UPS
  • C. Install an isolation transformer rated at K13 or K20
  • D. Install a passive harmonic filter on the UPS

Answer: B

Explanation:
Given the customer's requirement to limit Total Harmonic Distortion (THDi) to below 3% and the presence of a 6-pulse SCR/Thyristor-based rectifier, an active harmonic filter is the best solution. A 6-pulse rectifier typically generates higher harmonic distortion, often exceeding 3%, especially under substantial loads like 80%. An active harmonic filter dynamically monitors and compensates for harmonic distortion, effectively reducing THDi and supporting a more power-efficient operation, aligning with the customer's energy efficiency goals.
Detailed Explanation:
Passive harmonic filters can reduce harmonics but are less effective at maintaining low THDi levels under varying loads. Active filters offer real-time correction and can achieve lower THDi levels than passive filters, especially in systems with fluctuating loads or where strict harmonic limits are required. Installing an active harmonic filter will ensure compliance with the specified THDi limits and optimize power quality.
EPI Data Center Specialist References:
EPI guidance on power quality management recommends active harmonic filters for environments where strict THDi levels are necessary. Active filters offer better control over harmonic levels, supporting both compliance and operational efficiency.


NEW QUESTION # 51
You are allowed to use a calculator for this question. A battery bank is rated at a total capacity of 600 Ah. Calculate how much charging current the rectifier should be able to supply as charging current.

  • A. 80 Amperes
  • B. 60 Amperes
  • C. 12 Amperes
  • D. 30 Amperes

Answer: D

Explanation:
To determine the charging current for a battery bank, a general rule of thumb is that the charging current should be 5% of the total battery capacity. For a battery rated at 600 Ah, this calculation would be:
600 Ah×0.05=30 Amperes600 , text{Ah} times 0.05 = 30 , text{Amperes}600Ah×0.05=30Amperes This ensures the battery is charged efficiently without overloading the rectifier or risking battery damage.
Detailed Explanation:
Battery charging current is typically set as a percentage of the battery's capacity to balance effective charging with longevity and safety. A 5% charging rate is standard for lead-acid batteries, which would be 30 Amperes for a 600 Ah battery bank.
EPI Data Center Specialist References:
EPI standards recommend calculating charging currents based on a percentage of the battery capacity to ensure safety and efficiency, aligning with best practices for battery management in data centers.


NEW QUESTION # 52
You are allowed to use a calculator for this question.
A computer room has a net volume of approximately 2,500 m³ / 88,287 ft³.
The temperature is 20 °C / 68 °F.
The required design concentration is 7%.
The S-Factor is 0.1359 (metric) / 1.885 (imperial).
Calculate the amount of gas required for this computer room based on FM200. What is the correct weight?

  • A. Approximately 410 kg / 900 lbs
  • B. Approximately 1,390 kg / 3,000 lbs
  • C. Approximately 1,640 kg / 3,600 lbs
  • D. Approximately 820 kg / 1,800 lbs

Answer: D

Explanation:
The amount of FM200 gas required can be calculated using the formula:
Weight of Gas=Net Volume×Design Concentration×S-Factortext{Weight of Gas} = text{Net Volume} times text{Design Concentration} times text{S-Factor}Weight of Gas=Net Volume×Design Concentration×S-Factor Using metric units:
Net Volume: 2,500 m³
Design Concentration: 7% (or 0.07)
S-Factor: 0.1359
Calculation:
2,500 m3×0.07×0.1359=821.325 kg2,500 , text{m}